Autocall A4090-9008
Autocall A4090-9008
Only 2 left!
The Autocall A4090-9008 is an IDNet-communicating Dual Contact Relay IAM (individually addressable module) that lets a fire alarm control panel control two remotely located Form C contacts over a single IDNet address, using low-power latching relays that draw both data and operating power from the IDNet communications wiring. Typical uses include switching local power for elevator recall, or controlling HVAC components like fans and dampers, with each relay defaulting to OFF on initial power-up or if IDNet communications are lost.
Key Features
- Controls two independent 2A Form C relay contacts from one addressable point
- Relays default to OFF on power-up or loss of IDNet communications
- Compatible with Autocall 4007ES, 4010ES, and 4100ES control panels
- Mounts in a standard 4-inch square electrical box
Technical Specifications
- Contact Rating: 2A @ 30VDC resistive / 1A @ 30VDC inductive (power-limited); 0.5A @ 125VAC resistive (non-power-limited)
- Dimensions: 4-1/8 in H x 4 in W x 1-3/8 in D
- IDNet Wiring Distance: Up to 2,500 ft from the panel, 10,000 ft total
Certifications
- UL Listed to Standard 864
- CSFM Listed