Edwards SIGA-TCDR
Edwards SIGA-TCDR
Out of stock; call for lead time
The Edwards EST SIGA-TCDR is an intelligent addressable temporal pattern generator module for EST QuickConnect fire alarm systems. It provides separate audible alarm signals for fire and carbon monoxide detection by generating NFPA 72 temporal patterns (TC3 or TC4) from a single address. The module pairs with compatible AB4GT or AB4G-LF sounder bases to deliver code-compliant alarm notification.
Key Features
- Temporal pattern generation for fire and CO distinction on compatible sounder bases
- Two addressable channels for separate Fire (TC3) and CO (TC4) pattern control
- Supports AB4GT (CO-compatible) and AB4G-LF (520 Hz low-frequency) sounder bases
- SYNC signal synchronization for multi-device coordination
- Uses two SLC addresses (one per channel) on the signaling line circuit
- Powered by connected sounder base riser system
Technical Specifications
- Device Type: Addressable temporal pattern generator module
- Channels: Two (Channel 1: TC3/Fire, Channel 2: TC4/CO in US operation)
- Compatible Bases: SIGA-AB4GT, SIGA-AB4G-LF sounder bases
- Addressing: Two addresses on SLC (one per channel)
- Operation: US mode default; European mode available (Channel 1: TC4, Channel 2: TC3)
- Priority: Channel 1 has priority if both channels activated simultaneously
- Power: Supplied from connected sounder base riser
Certifications
- UL Listed addressable pattern generator module
- NFPA 72 temporal pattern compliant (TC3/TC4 or equivalent)