Gamewell FCI | SLC-PM
Module SLP Add-On SLC System Sensor 1 Loop-31
Gamewell-FCI SLC-PM Signaling Line Circuit Personality Module
The Gamewell-FCI SLC-PM is a plug-in Signaling Line Circuit (SLC) Personality Module designed for the S3 Series fire alarm control panels. It enables communication between the control panel and addressable devices, supporting both System Sensor Velociti® and CLIP™ protocols. This module facilitates system expansion and enhances the flexibility of fire alarm installations.
Key Features
-
High Device Capacity: Supports up to 318 System Sensor Velociti® devices (159 sensors and 159 modules) or up to 198 CLIP™ devices (99 sensors and 99 modules).
-
Flexible Wiring Options: Compatible with Class A or Class B wiring configurations, accommodating various installation requirements.
-
Plug-In Installation: Designed for easy plug-in installation into the SLP-E3 main board, simplifying system upgrades and expansions.
-
Low Power Consumption: Operates with a low current draw of 0.014 amps, ensuring energy-efficient performance.
-
Standard Operating Conditions: Functions within a temperature range of 32°F to 120°F (0°C to 49°C) and up to 93% relative humidity (non-condensing).
-
Regulatory Compliance: Listed per UL 864 9th Edition and approved by FM, MEA FDNY (COA #6162), CSFM, and City of Chicago Class 1.