Kidde GSA-CT2
Kidde GSA-CT2
In stock!
The Kidde GSA-CT2 is an intelligent, analog addressable dual input module that connects one or two Class B, normally-open dry-contact initiating device circuits to a Signature Series fire alarm loop controller. Each of its two input channels can independently report an alarm, supervisory, or trouble condition back to the panel from field devices like pull stations, waterflow switches, or tamper switches, and it addresses electronically on the Signature loop without DIP switches, consuming two device addresses since it monitors two circuits.
Key Features
- Two independent Class B dry-contact initiating device circuit inputs
- Reports alarm, supervisory, or trouble per channel to the Signature loop controller
- Electronic addressing, no DIP switches required
- Mounts to standard North American 1-gang or 4-inch square electrical boxes with a GSA-MP mounting plate
Technical Specifications
- Operating Voltage: 15.2-19.95 VDC
- Standby Current: 450 µA; Activated Current: 700 µA
- IDC End-of-Line Resistor: 47K ohm
- Operating Temperature: 32-120°F (0-49°C), 0-93% RH non-condensing
- Mounting: 2-1/2" deep 1-gang box or 1-1/2" deep 4" square box with GSA-MP plate
Certifications
- UL/ULC Listed dual input module